2
|
Troubleshooting
Possible failure
Expansion valve incorrect
control - superheat too
low.
2.4.8 Symptom: Abnormal presence of ice
Possible failure
General ice build-up.
Ice build-up on the
outdoor unit.
Defrost operation
malfunction.
Ice build-up at entry spot
of refrigerant.
Partial ice up of coil.
Service manual
74
Root cause category: component – electrical
Root cause
▪
Faulty
suction
thermistor,
▪
Faulty expansion valve
control.
Root cause
—
▪
Clogged drain holes,
▪
Snow on the outdoor
unit,
▪
Ice building up on the
casing.
NOT enough defrost
power: shortage of
refrigerant.
Refrigerant shortage.
Partial refrigerant
blockage.
Dirty coil.
Bad weather conditions.
Check
▪
Check
suction
thermistor,
▪
Check
the
expansion
valve.
Check
—
Ice is NOT in direct contact
with fins.
▪
Check refrigerant charge,
▪
Check for leaks.
▪
Check refrigerant charge,
▪
Check for leaks.
Check refrigerant circuit.
Check if coil is dirty.
Unit is NOT powerful
enough to defrost due to
too strong wind, snow, ...
Repair
▪
Replace thermistor when
required,
▪
Replace expansion valve
when required.
Repair
Outdoor unit installation
MUST be protected from
weather (wind, snow, ...).
See installer reference
guide for correct
installation.
▪
Unclog drain holes or
remove any scraps that
can be used for ice to
build up,
▪
Remove ice.
▪
Replace refrigerant,
▪
Fix leaks.
▪
Replace refrigerant,
▪
Fix leaks.
Replace part where
blockage occurs.
Clean coil.
Outdoor unit installation
MUST be protected from
weather (wind, snow, ...).
See installer reference
guide for correct
installation.
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03