Symptom: Abnormal Presence Of Ice - Daikin altherma 3 M Service Manual

Hide thumbs Also See for altherma 3 M:
Table of Contents

Advertisement

2
|
Troubleshooting
Possible failure
Expansion valve incorrect
control - superheat too
low.

2.4.8 Symptom: Abnormal presence of ice

Possible failure
General ice build-up.
Ice build-up on the
outdoor unit.
Defrost operation
malfunction.
Ice build-up at entry spot
of refrigerant.
Partial ice up of coil.
Service manual
74
Root cause category: component – electrical
Root cause
Faulty
suction
thermistor,
Faulty expansion valve
control.
Root cause
Clogged drain holes,
Snow on the outdoor
unit,
Ice building up on the
casing.
NOT enough defrost
power: shortage of
refrigerant.
Refrigerant shortage.
Partial refrigerant
blockage.
Dirty coil.
Bad weather conditions.
Check
Check
suction
thermistor,
Check
the
expansion
valve.
Check
Ice is NOT in direct contact
with fins.
Check refrigerant charge,
Check for leaks.
Check refrigerant charge,
Check for leaks.
Check refrigerant circuit.
Check if coil is dirty.
Unit is NOT powerful
enough to defrost due to
too strong wind, snow, ...
Repair
Replace thermistor when
required,
Replace expansion valve
when required.
Repair
Outdoor unit installation
MUST be protected from
weather (wind, snow, ...).
See installer reference
guide for correct
installation.
Unclog drain holes or
remove any scraps that
can be used for ice to
build up,
Remove ice.
Replace refrigerant,
Fix leaks.
Replace refrigerant,
Fix leaks.
Replace part where
blockage occurs.
Clean coil.
Outdoor unit installation
MUST be protected from
weather (wind, snow, ...).
See installer reference
guide for correct
installation.
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03