3.8.2 Repair procedures

To remove the compressor thermal protector
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
Does the compressor thermal protector
contact open and close at the correct
temperature?
Yes
No
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
Prerequisite: Remove the compressor insulation.
1 Disconnect the intermediate connector from the compressor thermal
protector.
2 Cut all tie straps that fix the compressor thermal protector wiring harness.
3 Remove the compressor thermal protector with bracket from the compressor
housing.
a b
a Compressor thermal protector
b Bracket
c Compressor
4 Separate the compressor thermal protector and the compressor thermal
protector bracket.
Action
Return to the troubleshooting of the
specific error and continue with the
next procedure.
Replace the compressor thermal
protector, see
"3.8.2 Repair
4
procedures" [
 147].
"3.17 Plate
c
3
Components
|
4
work" [
 230].
Service manual