Table 6-6
Maximum voltage peaks at the motor terminals for motors specifically designed for converter operation
Rated motor voltage
V
≤ 500 V
> 500 V to 690 V
Depending on the step height, the voltage rise times for the individual voltage steps in the line-
to-ground voltage at the motor end of the cable must not fall below the following values.
Table 6-7
Rise times as a function of voltage level
Step height
See also
Further documents (Page 130)
6.8

Final checks

Before closing the terminal box/terminal base of the machine enclosure, check the following:
• Establish the electrical connections in the terminal box in accordance with the information
in this documentation.
• Maintain the air clearances between non-insulated parts as described in Chapter Minimum
air clearances. (Page 68)
• Avoid protruding wire ends.
• In order not to damage the cable insulation, freely arrange the connecting cables.
• Connect the machine corresponding to the specified direction of rotation.
• Keep the inside of the terminal box clean and free from trimmed-off ends of wire.
• Ensure that all seals and sealing surfaces are undamaged and clean.
• Correctly and professionally close unused openings in the terminal boxes. Observe the
information in this documentation.
• Observe the information on torques in this documentation.
See also
Tightening torques for screw and bolt connections (Page 131)
1FZ shaft height 280
Operating Instructions, 02/2022, A5E51698698A
Û
phase-to-phase
V
pk
1600
2200
V
900
1050
1260
Maximum peak voltage at the motor terminals
Û
phase-to-ground
V
pk
1400
1500
Electrical connection
6.8 Final checks
DC link U
1080
Minimum rise time t
r
ns
100
200
400
DC
V
750
75