Ups Connection Without A Flexpdu Or Hotswap Mbp Module - Eaton EX Pulsar Series Installation And User Manual

Table of Contents

Advertisement

HotSwap MBP module operation
UPS start-up with the HotSwap MBP module
1.
2.
3.
LED (51) "UPS ON - OK to switch" on the HotSwap MBP module goes ON.
HotSwap MBP module test
1.
2.
2.7

UPS Connection Without a FlexPDU or HotSwap MBP Module

Check that the indications on the name plate located on the back of the UPS correspond to the AC power source
and the true electrical consumption of the total load.
i
Note: The UPS charges the battery as soon as it is connected to the AC power source, even if button (27) is not
i
pressed. Once the UPS is connected to the AC power source, eight hours of charging are required before the
battery can supply the rated backup time
2009 10:56:24
86-86710-00 A02 UM.indd 15
Check that the UPS is correctly connected to the HotSwap MBP module.
Set switch (53) to the Normal position.
Start the UPS by pressing the ON/OFF button (27) on the UPS control panel.
The load is supplied by the UPS.
Set switch (53) to the Bypass position and check that the load is still supplied.
Set switch (53) back to the Normal position.
The HotSwap MBP module has a rotary
switch (53) with two positions:
Normal – the load is supplied by the UPS,
LED (51) is ON.
Bypass – the load is supplied directly by
the AC power source. LED (52) is
ON.
1. Connect the input cord (31) (100V 30A / or
20A on EX 2200) to the AC power source.
2. Connect the loads to the UPS.
It is preferable to connect the priority loads
to the four outlets marked (9) and the
non-priority loads to the two outlets
marked (8) that can be programmed.
Connect any high-power devices to the
20A (or 30A on EX 3000) outlet (7) as
shown at left for EX 2200.
To program shutdown of outlets (8)
during operation on battery power and
thus optimise the available backup time,
the EATON communications software is
required.
11
2. Installation
86-86710-00EN A02 - Page 15
14/01/2009 10:56:26

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ex 2200 rt 2uEx 3000 rt 2uEx exb rt 3u

Table of Contents