Forcing Inputs and Outputs —
may be forced both from the CCN and directly at the local
display. This can be useful during diagnostic testing and also
during operation, typically as part of an advanced third party
control scheme. Please see Appendix A and B.
NOTE: In the case of a power reset, any force levels in effect
at the time of the power reset will be cleared.
CONTROL LEVEL FORCING — If any of the following
points are forced with a priority level of 7 (consult CCN litera-
ture for a description of priority levels), the software clears the
force from the point if it has not been written to or forced again
within the timeout periods defined below:
Temperatures
AIR.T
OAT Outside Air Temperature
Temperatures
AIR.T
RAT Return Air Temperature
Temperatures
AIR.T
SPT Space Temperature
Inputs
RSET
SP.RS
Static Pressure Reset
Inputs
REL.H
OA.RH
Outside Air Relative Humidity 30 minutes
Inputs
AIR.Q
OAQ
Outside Air Quality
VOLTAGE DROP
(v)
0.466
0.564
0.663
0.761
0.860
0.958
1.056
1.155
1.253
1.352
1.450
1.549
1.647
1.745
1.844
1.942
2.041
2.139
2.238
2.336
2.434
2.533
2.631
2.730
2.828
2.927
3.025
3.124
3.222
3.320
3.419
3.517
3.616
3.714
3.813
3.911
4.009
4.108
4.206
4.305
4.403
4.502
4.600
Many of variables
30 minutes
3 minutes
3 minutes
30 minutes
30 minutes
Run Status Menu —
user important information about the unit. The Run Status table
can be used to troubleshoot problems and to help determine
how and why the unit is operating.
AUTO VIEW OF RUN STATUS — The Auto View of Run
Status display table provides the most important unit informa-
tion. The HVAC Mode (Run Status
forms the user what HVAC mode the unit is currently in. Refer
to the Modes section on page 40 for information on HVAC
modes. The occupied status, unit temperatures, unit set points,
and stage information can also be shown. See Table 78.
Run Status
VIEW
Mode(s) by name. HVAC Modes include:
OFF
VENT
STARTING UP
HIGH COOL
SHUTTING DOWN
LOW COOL
DISABLED
UNOCC FREE COOL EVACUATION
SOFTSTOP REQUEST TEMPERING HICOOL SMOKE PURGE
REM SW DISABLE
TEMPERING LOCOOLDEHUMIDIFICATION
COMP STUCK ON
TEMPERING VENT
TEST
LOW HEAT
Run Status
VIEW
cy status of the control.
Run Status
VIEW
mixed-air temperature. This value is calculated based on
return-air and outside-air temperatures and economizer damper
position.
Run Status
VIEW
tor discharge air temperature during Cooling modes. This value
is read at the supply air thermistor location (or at cooling coil
thermistor array if unit is equipped with hydronic heating coil).
Run Status
VIEW
air temperature during Vent and Hydronic Heating modes. This
value is read at the supply air thermistor location.
Run Status
VIEW
mizer control point value (a target value for air temperature
leaving the evaporator coil location).
Run Status
VIEW
economizer position (in percentage open).
Run Status
VIEW
tion of actuator no. 2 (in percentage open).
Run Status
VIEW
ing control point (a target value for air temperature leaving the
evaporator coil location).
Run Status
VIEW
amount of unit cooling capacity (in percent of maximum).
Compare to staging tables in Appendix C.
Run Status
VIEW
of requested cooling stages. Compare to staging tables in
Appendix C and to C.CAP above.
Run Status
VIEW
ing control point, for use with staged gas control option only (a
target value for air temperature leaving the supply duct).
Run Status
VIEW
of heating stages active (for staged gas control option only).
Compare to following point.
Run Status
VIEW
number of heat stages available for this model.
90
The Run Status menu provides the
VIEW
HVAC) in-
HVAC — Displays the current HVAC
HIGH HEAT
FIRE SHUT DOWN
PRESSURIZATION
RE-HEAT
OCC — Displays the current occupan-
MAT — Displays the current value for
EDT — Displays the current evapora-
LAT — Displays the current leaving-
EC.C.P — Displays the current econo-
ECN.P — Displays the current actual
EC2.P — Displays the current posi-
CL.C.P — Displays the current cool-
C.CAP — Displays the current
CL.ST — Displays the current number
HT.C.P — Displays the current heat-
HT.ST — Displays the current number
H.MAX — Displays the maximum