Carrier WEATHERMASTER 48/50Z030-105 Operation And Service Manual page 176

Single package large rooftop units with comfortlink version 4.x controls
Hide thumbs Also See for WEATHERMASTER 48/50Z030-105:
Table of Contents

Advertisement

ITEM
BP (cont)
→FAN.T
→FAN.T→FT.CF
→FAN.T→FT.TM
→FAN.T→FT.ST
→FAN.T→FT.MX
→FAN.T→FT.AD
→FAN.T→FT.OF
→FAN.T→FT.RM
→FAN.T→FT.RS
→FAN.T→SCF.C
→B.PID
→B.PID→BP.TM
→B.PID→BP.P
→B.PID→BP.I
→B.PID→BP.D
→ACT.C
→ACT.C→BP.1
→ACT.C→BP.1→SN.1
→ACT.C→BP.1→SN.2
→ACT.C→BP.1→SN.3
→ACT.C→BP.1→SN.4
→ACT.C→BP.1→SN.5
→ACT.C→BP.1→C.A.LM
→ACT.C→BP.2
→ACT.C→BP.2→SN.1
→ACT.C→BP.2→SN.2
→ACT.C→BP.2→SN.3
→ACT.C→BP.2→SN.4
→ACT.C→BP.2→SN.5
→ACT.C→BP.2→C.A.LM
D.LV.T
→L.H.ON
→H.H.ON
→L.H.OF
→L.C.ON
→H.C.ON
→L.C.OF
→C.T.LV
→H.T.LV
→C.T.TM
→H.T.TM
DMD.L
→DM.L.S
→D.L.20
→SH.NM
→SH.DL
→SH.TM
→D.L.S1
→D.L.S2
IAQ
→DCV.C
→DCV.C→EC.MN
→DCV.C→IAQ.M
→DCV.C→O.C.MX
→DCV.C→O.C.MN
→DCV.C→O.C.DB
→AQ.CF
→AQ.CF→IQ.A.C
→AQ.CF→IQ.A.F
→AQ.CF→IQ.I.C
→AQ.CF→IQ.I.F
→AQ.CF→OQ.A.C
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
EXPANSION
FAN TRACKING CONFIG
Fan Track Learn Enable
Fan Track Learn Rate
Fan Track Initial DCFM
Fan Track Max Clamp
Fan Track Max Correction
Fan Track Internl EEPROM
Fan Track Internal RAM
Fan Track Reset Internal
Supply Air CFM Config
BLDG.PRESS.PID CONFIGS
Bldg.Pres.PID Run Rate
Bldg.Press. Prop. Gain
Bldg.Press. Integ. Gain
Bldg.Press. Deriv. Gain
BLDG.PRES. ACTUATOR CFGS
BLDG.PRES. ACT.1 CONFIGS
BP 1 Serial Number 1
BP 1 Serial Number 2
BP 1 Serial Number 3
BP 1 Serial Number 4
BP 1 Serial Number 5
BP1 Cntrl Angle Lo Limit
BLDG.PRES. ACT.2 CONFIGS
BP 2 Serial Number 1
BP 2 Serial Number 2
BP 2 Serial Number 3
BP 2 Serial Number 4
BP 2 Serial Number 5
BP2 Cntrl Angle Lo Limit
COOL/HEAT SETPT. OFFSETS
Dmd Level
Lo Heat On
Dmd Level(+) Hi Heat On
Dmd Level(-) Lo Heat Off
Dmd Level
Lo Cool On
Dmd Level(+) Hi Cool On
Dmd Level(-) Lo Cool Off
Cool Trend Demand Level
Heat Trend Demand Level
Cool Trend Time
Heat Trend Time
DEMAND LIMIT CONFIG.
Demand Limit Select
Demand Limit at 20 ma
Loadshed Group Number
Loadshed Demand Delta
Maximum Loadshed Time
Demand Limit Sw.1 Setpt.
Demand Limit Sw.2 Setpt.
INDOOR AIR QUALITY CFG.
DCV ECONOMIZER SETPOINTS
Economizer Min.Position
IAQ Demand Vent Min.Pos.
Economizer Min.Flow
IAQ Demand Vent Min.Flow
Econ.Min.Flow Deadband
AIR QUALITY CONFIGS
IAQ Analog Sensor Config
IAQ 4-20 ma Fan Config
IAQ Discrete Input Config
IAQ Disc.In. Fan Config
OAQ 4-20ma Sensor Config
RANGE
Yes/No
5-60 min
-20000 - 20000 CFM
0 - 20000 CFM
0 -20000 CFM
-20000 - 20000 CFM
-20000 - 20000 CFM
Yes/No
1 - 2 (multi-text strings)
5 - 120 sec
0 - 5
0 - 2
0 - 5
0 - 255
0 - 255
0 - 255
0 - 255
0 - 255
0-90
0 - 255
0 - 255
0 - 255
0 - 255
0 - 255
0-90
-1 - 2 ^F
0.5 - 20.0 ^F
0.5 - 2.0 ^F
-1 - 2 ^F
0.5 - 20.0 ^F
0.5 - 2.0 ^F
0.1 - 5.0 ^F
0.1 - 5.0 ^F
30 - 600 sec
30 - 600 sec
0 - 3 (multi-text strings)
0 - 100%
0 - 99
0 - 60%
0 - 120 min
0 - 100%
0 - 100%
0 - 100%
0 - 100%
0 - 20000 CFM
0 - 20000 CFM
200 - 1000 CFM
0 - 4 (multi-text strings)
0 - 2 (multi-text strings)
0 - 2 (multi-text strings)
0 - 2 (multi-text strings)
0 - 2 (multi-text strings)
CL-4
DEFAULT
SETTING
No
15
2000
4000
1000
0
0
No
1
10
0.5
0.5
0.3
0
0
0
0
0
35
0
0
0
0
0
35
1.5
0.5
1.0
1.5
0.5
1.0
0.1
0.1
120
120
0
100
0
0
60
80
50
5
0
2000
0
400
0
0
0
0
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents