Carrier WEATHERMASTER 48/50Z030-105 Operation And Service Manual page 177

Single package large rooftop units with comfortlink version 4.x controls
Hide thumbs Also See for WEATHERMASTER 48/50Z030-105:
Table of Contents

Advertisement

ITEM
IAQ (cont)
→AQ.SP
AIR QUALITY SETPOINTS
→AQ.SP→IQ.O.P
IAQ Econo Override Pos.
→AQ.SP→IQ.O.C
IAQ Override Flow
→AQ.SP→DAQ.L
Diff.Air Quality LoLimit
→AQ.SP→DAQ.H
Diff. Air Quality HiLimit
→AQ.SP→D.F.OF
DAQ PPM Fan Off Setpoint
→AQ.SP→D.F.ON
DAQ PPM Fan On Setpoint
→AQ.SP→IAQ.R
Diff. AQ Responsiveness
→AQ.SP→OAQ.L
OAQ Lockout Value
→AQ.SP→OAQ.U
User Determined OAQ
→AQ.S.R
AIR QUALITY SENSOR RANGE
→AQ.S.R→IQ.R.L
IAQ Low Reference
→AQ.S.R→IQ.R.H
IAQ High Reference
→AQ.S.R→OQ.R.L
OAQ Low Reference
→AQ.S.R→OQ.R.H
OAQ High Reference
→IAQ.P
IAQ PRE-OCCUPIED PURGE
→IAQ.P→IQ.PG
IAQ Purge
→IAQ.P→IQ.P.T
IAQ Purge Duration
→IAQ.P→IQ.P.L
IAQ Purge LoTemp Min Pos
→IAQ.P→IQ.P.H
IAQ Purge HiTemp Min Pos
→IAQ.P→IQ.L.O
IAQ Purge OAT Lockout
HUMD
HUMIDITY CONFIGURATION
→HM.CF
Humidifier Control Cfg.
→HM.SP
Humidifier Setpoint
→H.PID
HUMIDIFIER PID CONFIGS
→H.PID→HM.TM
Humidifier PID Run Rate
→H.PID→HM.P
Humidifier Prop. Gain
→H.PID→HM.I
Humidifier Integral Gain
→H.PID→HM.D
Humidifier Deriv. Gain
→ACT.C
HUMIDIFIER ACTUATOR CFGS
→ACTC→SN.1
Humd Serial Number 1
→ACTC→SN.2
Humd Serial Number 2
→ACTC→SN.3
Humd Serial Number 3
→ACTC→SN.4
Humd Serial Number 4
→ACTC→SN.5
Humd Serial Number 5
→ACTC→C.A.LM
Humd Ctrl Angle Lo Limit
DEHU
DEHUMIDIFICATION CONFIG.
→D.SEL
Dehumidification Config
→D.SEN
Dehumidification Sensor
→D.EC.D
Econ disable in DH mode?
→D.V.CF
Vent Reheat Setpt Select
→D.V.RA
Vent Reheat RAT offset
→D.V.HT
Vent Reheat Setpoint
→D.C.SP
Dehumidify Cool Setpoint
→D.RH.S
Dehumidify RH Setpoint
CCN
CCN CONFIGURATION
→CCNA
CCN Address
→CCNB
CCN Bus Number
→BAUD
CCN Baud Rate
→BROD
CCN BROADCST DEFINITIONS
→BROD→TM.DT
CCN Time/Date Broadcast
→BROD→OAT.B
CCN OAT Broadcast
→BROD→ORH.B
CCN OARH Broadcast
→BROD→OAQ.B
CCN OAQ Broadcast
→BROD→G.S.B
Global Schedule Broadcst
→BROD→B.ACK
CCN Broadcast Ack'er
→SC.OV
CCN SCHEDULES-OVERRIDES
→SC.OV→SCH.N
Schedule Number
→SC.OV→HOL.T
Accept Global Holidays?
→SC.OV→O.T.L.
Override Time Limit
→SC.OV→OV.EX
Timed Override Hours
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
EXPANSION
RANGE
0 - 100%
0 - 31000 CFM
0 - 1000
100 - 2000
0 - 2000
0 - 2000
-5 - 5
0 - 2000
0 - 5000
0 - 5000
0 - 5000
0 - 5000
0 - 5000
Yes/No
5 - 60 min
0 - 100%
0 - 100%
35 - 70 dF
0 - 4
0 - 100%
10 - 120 sec
0 - 5
0 - 5
0 - 5
0 - 255
0 - 255
0 - 255
0 - 255
0 - 255
0-90
0-3(multi-text strings)
1-3(multi-text strings)
Yes/No
0-1(multi-text strings)
0-8 delta F
55-95 dF
40-55 dF
10-90%
1 - 239
0 - 239
1 - 5 (multi-text strings)
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
0 - 99
YES/NO
0 - 4 HRS
0 - 4 HRS
CL-5
DEFAULT
SETTING
100
10000
100
700
200
400
0
0
400
0
2000
0
2000
No
15
10
35
50
0
40
30
1
0.3
0.3
0
0
0
0
0
85
0
1
Yes
0
0
70
45
55
1
0
3
On
Off
Off
Off
Off
Off
1
No
1
0