Carrier WEATHERMASTER 48/50Z030-105 Operation And Service Manual page 119

Single package large rooftop units with comfortlink version 4.x controls
Hide thumbs Also See for WEATHERMASTER 48/50Z030-105:
Table of Contents

Advertisement

BOARD
TERMINAL
NO.
NUMBER
TB-1 - POWER CONNECTION OR DISCONNECT (in Main Control Box)
11
L1 power supply
TB1
12
L2 power supply
13
L3 power supply
NEUTRAL (in Main Control Box)
Neutral
1
Neutral Power
CCN COMMUNICATIONS (in Main Control Box)
1
LEN +
2
LEN C
3
LEN –
4
24 vac
Comm Port
5
CCN +
7
CCN c
7
CCN –
8
Grd
TB201 - FIELD CONNECTIONS (in Main Control Box)
1
Remote Occupied/Economizer Enable 24 vac out
2
Remote Occupied/Economizer Enable 24 vac in
3
Not Used
4
OD Enthalpy Switch in
5
Fire Shut Down
6
Fire Shut Down
7
VAV Heater Interlock Relay
8
VAV Heater Interlock Relay
TB201
9
Humidifier Output, Ground
10
Humidifier Output, 24 VAC
11
Unit Alarm Output
12
Unit Alarm Output
13
Smoke Detector Alarm Input
14
Smoke Detector Alarm Input
15
Not Used
16
Not Used
TB202 - THERMOSTAT CONNECTIONS (in Main Control Box)
1
Thermostat R
2
Thermostat G
3
Thermostat W2
4
Thermostat W1
5
Thermostat Y2
6
Thermostat Y1
7
Not Used
8
Space Sensor TH
9
Space Sensor COM
TB202
10
Space Sensor Offset SW
Indoor Air IAQ Remote Sensor/Remote
11
Pot/Remote 4-20 mA
Indoor Air IAQ Remote Sensor/Remote
12
Pot/Remote 4-20 mA
13
Not Used
14
Not Used
15
Not Used
16
Not Used
TB203 - FIELD CONNECTIONS (in Main Control Box)
1
Ground
2
Demand Limit 4-20 mA (+)
3
Demand Limit 4-20 mA (-)
4
Supply Air Reset 4-20 mA (+)
5
Supply Air Reset 4-20 mA (-)
6
Outdoor Air IAQ 4-20 mA (+)
7
Outdoor Air IAQ 4-20 mA (-)
8
Space Humidity 4-20 mA (+)
TB203
9
Space Humidity 4-20 mA (-)
10
Not Used
11
Not Used
12
Not Used
13
Not Used
14
Not Used
15
Not Used
16
Not Used
LEGEND
IAQ — Indoor Air Quality
VAV — Variable Air Volume
Table 92 — Field Terminal Connections
DESCRIPTION
119
TYPE
208-230/460/575/380/-3-60, 400-3-50
208-230/460/575/380/-3-60, 400-3-50
208-230/460/575/380/-3-60, 400-3-50
5 vdc, logic
5 vdc, logic
5 vdc, logic
24 vac
5 vdc, logic
5 vdc, logic
5 vdc, logic
ground
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
24 vac
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
external contact (maximum 24 vac, 3 A)
24 vac output
24 vac input
24 vac input
24 vac input
24 vac input
24 vac input
Thermistor input
Thermistor input
Thermistor input
Thermistor input or externally powered 4 to 20 mA when used with
180 ohm resistor
Thermistor input or externally powered 4 to 20 mA when used with
180 ohm resistor
ground
4 to 20 mA loop power
4 to 20 mA loop power
4 to 20 mA loop power
4 to 20 mA signal
4 to 20 mA loop power
4 to 20 mA signal
4 to 20 mA loop power
4 to 20 mA signal