Nortel DMS-100 Series Maintenance Manual page 61

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

The rotation cycle for week 2 that uses the default start time of 11 P.M. and the
default discharge time of 60 min appears in the following table. The legend
for the following table is as follows:
Table 8 Cycle rotation for week
Wk
Sunday
22:00
MEAS
ALL
2
O/C ST1
system marks the string as failed. The system returns the pair to the load
bus and the charge cycle for the next string starts.
Note 1: When a system software marks a battery string pair as failed,
follow the test procedures listed under "Manual test procedures for
system-failed battery strings".
Note 2: The battery string pair can return to service when either of the
following conditions occurs:
the system replaces a battery string pair that failed system testing
the user manually tests a battery string pair that passed system
testing
To RTS the battery string pair, use the BSY and RTS commands to manual
busy and return to service the PES.
O/C open circuit
STn battery string pair
CHG charge bus
DISCHG discharge through NT8X02 BCC card
MEAS measure voltage
LDB load bus
TST test.
Monday
Tuesday
6:00
O/C ST1
22:00
TST OCC
1
DCHG
ST1
23:00
23:00
DMS-100 Family OPM Maintenance Manual ISN07 (TDM)/SN07 (DMS) and up
OPM maintenance summary 1-45
Wednesday
Thursday
6:00
6:00
O/C ST2
O/C ST3
23:00
23:00
Friday
Saturday
6:00
6:00
O/C ST0
O/C ST1
23:00
23:00