Vfd Programming Parameters - Trane Voyager RT-SVX17C-EN Installation Operation & Maintenance

Commercial 27 1/2 to 50 ton 60 hz commercial 23 to 42 ton 50 hz cv or vav rooftop air conditioners with reliatel controls
Table of Contents

Advertisement

COMPONENT
FAILURE RESPONSE
(CFS) Clogged Filter
This input is for "indication"
Switch
only and does not effect
the normal operation
of the unit.
(FFS)
Unit will not operate in
Supply Fan Proving
any mode.
Switch
(SPT)
IGV will not open
Static Pressure
Transducer VAV
*NONE* = No LED indication
Table 29
Supply and Exhaust Fan VFD Programming Parameters
Menu
Parameter Description
102
Motor Power
Load
&
103
Motor Voltage Set Based on Motor Nameplate
Motor
105
Motor Current Set Based on Motor Nameplate
106
Motor RPM
Reference
&
215
Current Limit
Limits

VFD Programming Parameters

Units shipped with an optional variable frequency drive
(VFD) are preset and run tested at the factory. If a problem
with a VFD occurs, ensure that the programmed parameters
listed in Table 25 have been set before replacing the drive.
Note: Check to make sure that parameter 104 is set
to 60 Hz. To check parameter 104 press the
Extended Menu button, press the Left Arrow button
until menu Load & Motor is shown, press the up
arrow until parameter 104 is displayed. Parameter
104 can then be modified by pressing the Change
Data button and then the Up Arrow button. When
the desired selection has been made press the OK
button.
Should replacing the a VFD become necessary, the re-
placement is not configured with all of Trane's operating pa-
rameters. The VFD must be programmed before attempting
to operate the unit.
To verify and/or program a VFD, use the following steps:
1. Remove the mode input (RTRM J6-2 and J6-4) or turn
the NSB panel to OFF so that the fan will not attempt to
start during programming.
Component Failure Mode (Continued)/VFD Programming Parameters
NORMAL RANGE
Normal operation =
0 VAC measured
between terminals
J5-1 and Ground.
0.5" W.C.
Normally Open
0.25 - 4 VDC
between J8 and J9
on VAV
Setting
Set Based on Motor Nameplate
Set Based on Motor Nameplate
1 x Rated Current
DIAGNOSTIC
SERVICE LED ON
2-30 VDC present at
RTRM J6-6 and J6-10
Service Failure Output
at RTRM J6-6 to J6-10
"SERVICE" LED blinks
at ZSM
Heat and Cool Failure
Output at RTRM J6-7 to J6-6
& RTRM J6-8 to J6-6
"HEAT" and "COOL" LED's
blink at ZSM
Description
Set only for applications using 3hp Hi-
Efficiency motors. Set to 2.2 kW.
Set only for 200/230v 60hz & 380/415
50hz applications
Sets the motor FLA
Sets the motor RPM
Limits the maximum current to motor
WARNING
Hazardous Voltage! w/Capacitors!
Disconnect all electric power, including remote discon-
nects before servicing. Follow proper lockout/tagout pro-
cedures to ensure the power cannot be inadvertently en-
ergized. For variable frequency drives or other energy
storing components provided by Trane or others, refer to
the appropriate manufacturer's literature for allowable
waiting periods for discharge of capacitors. Verify with an
appropriate voltmeter that all capacitors have dis-
charged. Failure to disconnect power and discharge ca-
pacitors before servicing could result in death or serious
injury.
Note: For additional information regarding the safe dis-
charge of capacitors, see PROD-SVB06A-EN
HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK 1TB1
OR UNIT DISCONNECT SWITCH 1S14.
2. To modify parameters:
(a) Press the Extended Menu button
(b) Press the Left or Right Arrow button to scroll
through menus
(c) Press the up or down arrow to scroll through
parameter settings within a specified menu
(d) Press the Change Data button to allow a parameter