Trane Voyager RT-SVX17C-EN Installation Operation & Maintenance page 74

Commercial 27 1/2 to 50 ton 60 hz commercial 23 to 42 ton 50 hz cv or vav rooftop air conditioners with reliatel controls
Table of Contents

Advertisement

COMPONENT
FAILURE RESPONSE
(ZTEMP) Zone
1. No Heating or Cooling
Temperature Sensor
ZSM "Fan" selection
CV or VAV during
switch operates IDM
Unoccupied mode.
during Unoccupied Mode
TC01, TCO2, TC03
Heat goes off, IDM runs
High Temp Limit
continuously.
(LPC1) Low Pressure
Compressor CPR1
Control
will not operate.
(LPC2) Low Pressure
Compressor CPR2
Control
will not operate.
Dual Circuits Only
(CCB1)
Compressor CPR1
will not operate.
(CCB2 or CCB3)
Compressor CPR2 or
Compressor Overload CPR3 will not operate.
(HPC1) High Pressure Compressor CPR1
Control
will not operate.
(HPC2) High Pressure Compressor CPR2 or
Control
CPR3 will not operate.
(WTL1) Winding
Compressor CPR1
Temperature Limit
will not operate.
(WTL2 or WTL3)
Compressor CPR2 or
Winding Temperature
CPR3 will not operate.
Limit
(CC1) Compressor
Compressor CPR1
Contactor
will not operate.
24 VAC coil
(CC2 or CC3)
Compressor CPR2 or
Compressor Contactor CPR3 will not operate.
24 VAC coil
*NONE* = No LED indication
Component Failure Mode (Continued)
NORMAL RANGE
If RTRM senses a zone temp
input and then it is lost,
-40 TO 150 F
CV Cool Failure Output
346K to 2.1K
at RTRM J6-8 to J6-6
"COOL" LED Blinks
at ZSM
Normally Closed
Heat Failure Output
Open 135 F
at RTRM J6-7 to J6-6
Reset 105 F.
"HEAT" LED Blinks at ZSM.
Open 7 PSIG
Possible Cool Failure at
Close 22 PSIG.
RTRM J1-8 to Ground, 0 VAC.
"COOL" LED Blinks at ZSM.
Open 7 PSIG
Possible Cool Failure at
Close 22 PSIG.
RTRM J3-2 to Ground, 0 VAC.
"COOL" LED blinks at ZSM.
Normally Closed
Cool Failure Output
range varies by unit.
at RTRM J6-8 to J-6
"COOL" LED blinks at ZSM.
Normally Closed
Cool Failure Output
range varies by unit
at RTRM J6-8 to J-6
"COOL" LED blinks at ZSM.
Open 425 psig
Cool Failure Output
Close 325 psig
at RTRM J6-8 to J-6
"COOL" LED blinks at ZSM.
Open 425 psig
Cool Failure Output
Close 325 psig
at RTRM J6-8 to J-6
"COOL" LED blinks at ZSM.
Normally Closed
Cool Failure Output
at RTRM J6-8 to J-6
"COOL" LED blinks at ZSM.
Normally Closed
Cool Failure Output
at RTRM J6-8 to J-6
"COOL" LED blinks at ZSM.
Varies by unit
Cool Failure Output
at RTRM J6-8 to J-6
"COOL" LED blinks at ZSM.
Varies by unit
Cool Failure Output
at RTRM J6-8 to J-6
"COOL" LED blinks at ZSM.
74