Samsung AC009BNLDCH Service Manual page 236

Hide thumbs Also See for AC009BNLDCH:
Table of Contents

Advertisement

Troubleshooting
Test operation mode and check mode (Cont.)
■ View Mode
K4 short
Display contents
push
1
Order frequency
2
Current frequency
The number of preset indoor
3
units
4
Ambient temperature sensor
5
Compressor discharge sensor
6
Eva-Mid sensor
7
Condensor sensor
8
Current
9
Outdoor fan RPM
10
Target discharge temperature
11
EEV
The capacity sum of indoor
12
units
13
Protective control
14
IPM temperature
The number of connected
15
indoor units
16
ESC EEV(CAM)
17
ESC IN sensor
18
ESC OUT sensor
19
View mode end
1) Sub-zero temperatures are expressed as a minus, instead of hundreds digit.
2) The temperature unit can be switched between Celsius and Fahrenheit through Setting outdoor unit option switches.
(Default value is Celsius.)
3) If the temperature unit is set to Fahrenheit through Setting outdoor unit option switches, the value is expressed
in the unit of kBtu/h.
4-42
SEG1
SEG2
1
Hundreds digit
2
Hundreds digit
3
Hundreds digit
4
Hundreds digit or - ¹⁾
5
Hundreds digit
6
Hundreds digit or - ¹⁾
7
Hundreds digit or - ¹⁾
8
Tens digit
9
Thousands digit
A
Hundreds digit or - ¹⁾
B
Hundreds digit
C
Tens digit
0: Cooling
D
1: Heating
E
Hundreds digit or - ¹⁾
F
Hundreds digit
G
Hundreds digit
H
Hundreds digit or - ¹⁾
Hundreds digit
I
or - ¹⁾
BLANK
BLANK
SEG3
Tens digit
Tens digit
Tens digit
Tens digit
Tens digit
Tens digit
Tens digit
The first place of
Units digit
Hundreds digit
Tens digit
Tens digit
The first place of
Unit digit
Protective control
Frequency status
0: No Protective control
1: Freezing
2: Non-stop defrosting
3: Over-load
4: Discharge
4: Down_limit
5: Total electric current
Tens digit
Tens digit
Tens digit
Tens digit
Tens digit
BLANK
SEG4
Unit
Units digit
Hz
Units digit
Hz
Units digit
EA
Units digit
℃ or ℉ ²⁾
Units digit
℃ or ℉ ²⁾
Units digit
℃ or ℉ ²⁾
Units digit
℃ or ℉ ²⁾
A
decimals
Tens digit
rpm
Units digit
℃ or ℉ ²⁾
Units digit
step
kW or
decimals
kBtu/h ³⁾
0: Normal
1: Hold
-
2: Down
3: Up_limit
Units digit
℃ or ℉ ²⁾
Units digit
EA
Units digit
step
Units digit
℃ or ℉ ²⁾
Units digit
℃ or ℉ ²⁾
BLANK
Samsung Electronics

Hide quick links: