Troubleshooting
Option
SEG13
Function
Page
Indication
Details Indication
Indication
and details
2
Option
SEG19
Function
Page
Indication
Details Indication
Indication
and details
3
• 1) SEG4
By SEG4 setting, Minimizing fan operation when thermostat is off.
- Fan operates for 20 seconds at an interval of 5 minutes in heat mode.
- Fan stops or operates Ultra low in Cooling when thermostat is off.
• 2) SEG8
Even if you set the Use of drain pump option to 0, it is utomatically set to 2 (the drain pump is used with 3 minute delay).
• 3) SEG11
Compensation of the wind-free fan RPM option adjusts 20 rpm per 1 step.
• 4) SEG18
If you set the Maximum filter usage time option to a value other than 2 and 6, it is automatically set to 2 (1000 hours).
• 5) SEG20
If you set the Individual control with remote control option to a value other than 0 to 4, it is automatically set to 0 (Indoor 1)
• 6) SEG21
Default value of Heating setting compensation is 9°F(5℃).
• 7) SEG23
Soft Off: The indoor unit turns off its operation at the indicated time in the table for Installation Option after its final motion detection. But, it turns on again if the
MDS detects motion.
Hard Off: Designated time after SOFT OFF, it cannot turn on automatically when it detects motion. Users should control to turn on the indoor unit with remote
control, etc.
4-16
SEG14
Use of external control
Details
0
Disuse
Sub,
1
On/Off
Existing
2
Off
control
Window
3
On/Off
4
Disuse
Main,
5
On/Off
Existing
6
Off
control
Window
7
On/Off
8
Disuse
Sub,
9
On/Off
Reverse
A
Off
control
Window
B
On/Off
C
Disuse
Main,
D
On/Off
Reverse
E
Off
control
Window
F
On/Off
SEG20
SEG21
Individual control with
Heating setting
5)
remote control
compensation
Details
Indication
0 or 1
Indoor1
0
2
Indoor2
1
3
Indoor3
2
4
Indoor4
SEG15
SEG16
Setting the output of
extermal control
Indication
Details
0
Thermo on
Reserved
Operation
1
On
SEG22
Setting the MDS Kit installation option
6)
Details
Indication
Default
Standard
3.6˚F(2˚C)
Premium
Reserved
Standard
9˚F(5˚C)
Premium
SEG17
Buzzer control
Indication
Details
Indication
0
Use of buzzer
Disuse of
1
buzzer
7)
SEG23
Details
Disuse (Soft Off+Hard off)
0
Off after 20 min.
1
(Soft Off+Hard off)
Off after 40 min.
2
(Soft Off+Hard off)
Off after 80 min.
3
(Soft Off+Hard off)
Off after 20 min.
4
(Soft Off+Hard off)
Off after 40 min.
5
(Soft Off+Hard off)
Off after 80 min.
6
(Soft Off+Hard off)
Off after 20 min.
7
(Soft Off only)
Off after 40 min.
8
(Soft Off only)
Off after 80 min.
9
(Soft Off only)
Off after 20 min.
A
(Soft Off only)
Off after 40 min.
B
(Soft Off only)
Off after 80 min.
C
(Soft Off only)
Samsung Electronics
SEG18
Maximum filter
4)
usage time
Details
1000
2
hours
2000
6
hours
SEG24
Reserved