Diagnostic Checklist; Test Operation Mode And Check Mode - Samsung AC009BNLDCH Service Manual

Hide thumbs Also See for AC009BNLDCH:
Table of Contents

Advertisement

4-3. Diagnostic Checklist

4-3-1. Test operation mode and check mode

■ Display Options key
Key
Push type
Mode
1st
Heating test mode
K1
Short
2nd
Defrost test mode ¹⁾
3rd
End Key operation
1st
Cooling test mode
2nd
Inverter check
3rd
Pump down
4th
Unuesal
Inverter Fault
5th
K2
Short
Detection (Comp#1)
6th
Auto trial operation
Auto check
7th
(Installtion
commissioning mode)
8th
End Key operation
Reset Release Eco
K3
Short
1st
mode
1) Defrost test mode
Condition 1: The outdoor temperature is below 10°C.
Condition 2: All the temperature conditions should meet the defrost conditions.
2) Indication on the display and action to take when an inverter fault is detected
SEG1
SEG2
SEG3
Fault
detection
is in
progress
OK
NG
Check
Going
into fault
detection
mode
failed
3) Auto check (Installation commissioning mode)
To ensure normal operation of the product, first make sure to complete auto
check.
.
※ AC***BXSCCC series are not allowed to proceed K1 key test operation mode
due to cooling only models.
Samsung Electronics
Display
SEG 1
SEG 2
SEG 3
2)
3)
Action to
SEG4
take
-
-
PBA defect:
Replace the
PBA
Manual
7-segment display
7-segment display
inspection is
required
Try fault
detection
again
<AC024/030/036/042/048BXADCH,
AC030/036BXSCCC, AC030/036BXSCCH>
SEG 4
7-segment display
7-segment display
Key Switch
Key Switch
<AC009/012/018BXADCH, AC018/024BXSCCC>
Key Switch
Key Switch
Troubleshooting
4-41

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents