ADSU Supported Commands and Responses

ADSU Command and Responses
Mnemonic
C_SC_TA_1
C_DC_TA_1
C_RC_TA_1
C_BO_TA_1
C_SE_TA_1
C_SE_TB_1
C_SE_TC_1
Note:
Command Age: The value for this field is fixed to 5000 milliseconds. Time tagged
commands must have a time tag no older than this period or the control operation will not
take place.
1.7.6

General Purpose ADSUs Supported

General Purpose ADSUs supported
Mnemonic
C_IC_NA_1
C_CS_NA_1
1.8

Performance and Limitation

1.8.1

General Restrictions

Topic
Ethernet parameters
Introduction
Number
58
59
60
64
61
62
63
The commands are time tagged and only valid for the Command Age time.
Number
100
103
Notes
The IEC 104 server application code is developed on top of the RX3i ETM001
platform and is configured as an IC695EIS001 in the PAC Machine Edition E
hardware configuration. The module is limited to IPV4 addressing and can
accept AUP file settings for module parameters. Refer to the PACSystems
RX7i & RX3i TCP/IP Ethernet Communications User Manual, GFK-2224 for
more information.
Description
Single command with time tag CP56Time2a
Double command with time tag CP56Time2a
Regulating step command with time tag CP56Time2a
Bit String Response with time tag CP56Time2a
Measured value, normalized value command with time tag
CP56Time2a
Measured value, scaled value command with time tag CP56Time2a
Measured value, short floating-point number command with time
tag CP56Time2a
Description
Interrogation command
Clock synchronization command
Chapter 1