Table 5:

Standby Load Battery Size in Ah

Standby Load Battery Size Chart
Grand Total Standby Current
100 mA to 200 mA
201 mA to 300 mA
301 mA to 400 mA
401mA to 500 mA
501 mA to 600 mA
601 mA to 700 mA
701 mA to 800 mA
801 mA to 900 mA
901 mA to 1000 mA
1001 mA to 1100 mA
1101 mA to 1200 mA
Alarm Load Battery Size Chart
Grand Total Standby Current
250 mA to 500 mA
501 mA to 999 mA
1.0 A to 1.5 A
1.6 A to 2.0 A
2. 1 A to 2.5 A
2.6 A to 3.0 A
3. 1 A to 3.5 A
3.6 A to 4.0 A
4. 1 A to 4.5 A
4.6 A to 5.0 A
5. 1 A to 5.5 A
2. 1 1. 1

Compatible Devices

Table 6:

Compatible Devices

Device
D7014 Class "A" Zone
Converter
D7015 Class "A" NAC
Converter
D7030 Eight-Point LED
Annunciator
D7030X Eight Point LED
Annunciator
D7030X-S2 Eight Point
LED Annunciator
Bosch | 7/05 | 31499J
Capacity
Required for
24 H
5.8
8.6
11.5
14.4
17.3
20.2
23.0
25.9
28.8
31.7
34.6
Capacity
Required for
5 Min
0. 1
0. 1
0.2
0.2
0.3
0.3
0.4
0.4
0.5
0.5
0.6
Description
Converts a Class "B", Style B initiating circuit on the control panel to a Class "A", Style D circuit for
connection to field wiring. This module connects to one of the control panel's conventional inputs.
Converts a reversing Class "B" NAC to a Class "A" circuit. Compatible with any Class "B", Style Y
NAC that uses a 2.21 kΩ EOL resistor. When used on a Class "B", Style Y NAC, it implements a
Class "A", Style Z NAC. This connects to NAC output on the control panel.
Identifies the location of a fire alarm for up to eight zones, and up to eight are allowed for each sys-
tem.
Identifies the location of a fire alarm for up to eight zones, and up to eight are allowed for each sys-
tem.
An eight-zone LED annunciator, of which two zones are reserved for supervisory functions. It has
Power and Trouble LEDs plus eight zone LEDs that can be individually labeled.
D7024 | Operation and Installation Guide | 2.0 Overview
Capacity
Capacity
Required for
Required for
48 H
60 H
11.5
14.4
17.3
21.6
23.0
28.8
28.8
36.0
34.6
X
X
X
X
X
X
X
X
X
X
X
X
X
Capacity
Capacity
Required for
Required for
10 Min
15 Min
0. 1
0.2
0.2
0.3
0.3
0.5
0.4
0.6
0.5
0.8
0.6
0.9
0.7
1. 1
0.8
1.2
0.9
1.4
1.5
1.5
1. 1
1.7
Capacity
Capacity
Required for
Required for
72 H
80 H
17.3
19.2
25.9
28.8
34.6
38.4
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Capacity
Capacity
Required for
Required for
30 Min
45 Min
0.3
0.5
0.6
0.9
0.9
1.4
1.2
1.8
1.5
2.3
1.8
2.7
2. 1
3.2
2.4
3.6
2.7
4. 1
3
4.5
3.3
5