Checking The Anode Protective Current With An Anode Tester; Checking The Magnesium Anode; Replacing The Magnesium Anode; Checking The Firm Seating Of Electrical Connections - Viessmann Vitocal 222-G Installation And Service Instructions Manual

Compact heat pumps, 400 v~ and 230 v~
Hide thumbs Also See for Vitocal 222-G:
Table of Contents

Advertisement

Commissioning, inspection, maintenance

Checking the anode protective current with an anode tester

1. Remove cover and pull earth cable
See Fig. in chapter "Cleaning the DHW cylinder".

Checking the magnesium anode

We recommend replacing the magnesium anode once
it has been reduced to a diameter of 10 to 15 mm.

Replacing the magnesium anode

Note
If the magnesium anode needs to be replaced, a main-
tenance-free impressed current anode (accessories)
can be used.
Magnesium anode removal: See Fig. in chapter
"Cleaning the DHW cylinder"

Checking the firm seating of electrical connections

Closing the heat pump

See page 36.

Switching the power on

Switch on the mains power at the main MCB/fuse.

Commissioning the system

Commissioning (configuration, parameter settings and
function check) can be carried out with or without the
commissioning wizard (see following chapter and serv-
ice instructions for the heat pump control unit).
42
2. Connect the tester (measuring range up to 5 mA)
A
from tab
B
:
in series across tab
Anode pro-
tective cur-
rent
> 0.3 mA
< 0.3 mA
!
Please note
A short circuit between the magnesium anode
and the internal indirect coil negates the protec-
tive effect of the magnesium anode. This leads
to corrosion damage on the DHW cylinder.
Before connecting the electrical cables, check
the resistance across terminals
Fig. in chapter "Cleaning the DHW cylinder"). If
the resistance is significantly less than infinity,
check whether the magnesium anode is touch-
ing the internal indirect coil.
Note
The type and extent of the parameters depend on the
appliance type, on the selected system scheme and
the accessories employed.
B
and earth cable
A
Magnesium anode
Function OK
Visual inspection required: See
chapter "Checking the magnesium
anode".
and
A
.
(see
B

Advertisement

Table of Contents
loading

Table of Contents