Checking the sensors

Viessmann Pt500A (green marking)

860
780
700
620
540
460
-20
20
60
Temperature in °C
Fig. 51

Checking the fuses

For fuse locations, see page 23 onwards.
Fuse F1 is located on the mains terminal of the heat
pump control unit.
Fuse F3 is located on the main PCB.
Danger
Removing the fuse does not switch the power
circuit to zero volt. Contact with 'live' compo-
nents can lead to serious injury from electric cur-
rent.
Before working on the equipment, always
ensure that the power circuit is also at zero
volt.
(cont.)
100
140
180
Fuses F1 and F3:
6.3 A (slow), 250 V~
Max. power loss
2.5 W