Heat Pump Control Unit Power Supply 230 V - Viessmann Vitocal 300-A Installation And Service Instructions Manual

Air/water heat pump with electric drive, 400 v~
Table of Contents

Advertisement

Installation sequence
Power supply
(cont.)
Danger
Incorrect core assignment can lead to serious
injury from electrical current and result in appli-
ance damage.
Never interchange cores "L" and "N".
In negotiations with your power supply utility, differ-
ent supply tariffs for the main power circuits may be
offered.
Observe the technical connection conditions of the
power supply utility.
If the compressor and/or instantaneous heating
water heater are operated at an economy tariff
(power-OFF), either provide an additional cable (e.g.
2
3 x 1.5 mm
) for the power-OFF signal from the dis-
tribution board (meter box) to the heat pump control
unit.
or
Combine the cables for the power-OFF signal and
for the heat pump control unit power supply
2
(3 x 1.5 mm
) in a 5-core cable.
The assignment of the power-OFF (for compressor
and/or instantaneous heating water heater) is made
via the type of connection and by setting parameters
in the heat pump control unit.
In Germany, the power supply can be cut for a maxi-
mum of 3 x 2 hours per day (24 h).
The heat pump control unit/PCB must be supplied
without power-OFF. Tariffs subject to possible shut-
down must not be used here.

Heat pump control unit power supply 230 V~

A
max.16 A
X3.18
L1
X2.1
N
X1.1
?
Fig. 33
Mains terminals inside the heat pump control unit
A
Note
This supply must never be blocked.
40
1/N/PE
230 V / 50 Hz
When using power generated on site (use of power
generated by the PV system to meet own require-
ments):
During the power-OFF period, it is not possible to
operate the compressor utilising power generated on
site.
Protect the power cable to the heat pump control unit
with an MCB/fuse of max. 16 A.
For accessories and external components that will
not be connected to the heat pump control unit, pro-
vide the power supply via the same MCB/fuse, or at
least on the same phase, as the heat pump control
unit.
Connection to the same MCB/fuse provides addi-
tional safety when the power is switched off.
Observe the power consumption of the connected
consumers.
The PE wire of the power cable must be approx.
10 mm longer than the N and L wires.
Information regarding the compressor power sup-
ply
!
Please note
An incorrect phase sequence can cause dam-
age to the appliance.
Make the compressor power supply only in
the phase sequence specified (see terminals)
with a clockwise rotating field.
Characteristics of the compressor power fuses: see
"Specification".
Max. fuse rating 16 A
Standard tariff: No optional economy tariff with
power-OFF for the heat pump control unit
Recommended power cable:
3 x 1.5 mm
2
Recommended power cable with power-OFF for
compressor/ instantaneous heating water heater:
2
5 x 1.5 mm