Honeywell TC500A Integration Manual page 71

Hide thumbs Also See for TC500A:
Table of Contents

Advertisement

Feature
PICS statement
Output Object Read /
Write
Output Object Read /
Write
Output Object Read /
Write
FIRMWARE
Situational BACnet guidelines for TC500A
Table 31:
BACnet guidelines for TC500A
Limitation / Behavior
Reference input and output
is claimed in the PIC
statement, but the
corresponding objects is not
there in thermostat
Priority array values are not
synchronized with actual for
AO, MSO, & BO in Niagara
Set operation on AO, BO &
MSO is writing values to the
priority-16 instead of
relinquish default
If user configure binary
input or output in UIO
terminal and the
corresponding values has to
be refereed in analog input
or output object instead of
binary input or output in
Niagara
Thermostat firmware &
application download does
not support by Niagara
(start restore and end
restore service is missing)
(Continued)
Description
NA
NA
NA
NA
NA
Workaround
NA
NA
NA
NA
3rd party tool like
YABE can be used for
firmware download
71

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents