Honeywell TC500A Integration Manual page 21

Hide thumbs Also See for TC500A:
Table of Contents

Advertisement

Name
Cfg_FanSpeed_Heat1Mod
e
Cfg_FanSpeed_Heat2Mod
e
Cfg_FanMinSpeed_ModH
eat
Cfg_FanMaxSpeed_ModH
eat
Cfg_FanSpeed_DefaultMo
de
Cfg_FanSpeed_Speed1
Cfg_FanSpeed_Speed2
Cfg_FanSpeed_Speed3
Cfg_FanSpeed_Speed4
Cfg_FanSpeed_Speed5
Cfg_FanSpeed_Speed6
Fan configuration
Table 6:
Fan configuration
Default
Range
Value
1 = Speed1
1
2 = Speed2
3 = Speed3
4 = Speed4
5 = Speed5
6 = Speed6
1 = Speed1
1
2 = Speed2
3 = Speed3
4 = Speed4
5 = Speed5
6 = Speed6
40 to 100%
40
40 to 100%
100
1 = Speed1
1
2 = Speed2
3 = Speed3
4 = Speed4
5 = Speed5
6 = Speed6
40 to 100%
100%
40 to 100%
100%
40 to 100%
100%
40 to 100%
100%
40 to 100%
100%
40 to 100%
100%
(Continued)
BACnet
BACnet
Object
Point Type
Instance
ID
BACnet
17
ENUM Value
BACnet
18
ENUM Value
BACnet
83
Numeric
Value
BACnet
84
Numeric
Value
BACnet
19
ENUM Value
BACnet
64
Numeric
Value
BACnet
65
Numeric
Value
BACnet
66
Numeric
Value
BACnet
67
Numeric
Value
BACnet
68
Numeric
Value
BACnet
69
Numeric
Value
Description
Fan speed selection for
Heating/Aux Heat Single
Stage.
Fan speed selection for
Heating/Aux Heat Multiple
Stages.
Fan minimum speed
selection for modulating
heat
Fan maximum speed
selection for modulating
heat
Fan speed selection for
Default mode.
Fan speed 1
Fan speed 2
Fan speed 3
Fan speed 4
Fan speed 5
Fan speed 6
21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents