Control Configuration - Honeywell TC500A Integration Manual

Hide thumbs Also See for TC500A:
Table of Contents

Advertisement

Control configuration

Name
Cfg_Control_MainSensor
Cfg_Control_PowerupDelay
Cfg_Control_SmokeMode
Control configuration
Table 15:
Control configuration
Default
Range
Value
1 = Local Temp/
1 = Local
Hum
Temp/
2 = Remote
Hum
Temp/ Hum
3 = Multi Temp/
Hum
0-300 Sec
10
1 = No Override
1 (No
2 = Shutdown
Override)
3 = Pressurize
4 = Depressurize
BACnet
BACnet
Object
Point
Instance
Type
ID
BACnet
9
ENUM
Value
BACnet
14
Numeric
Value
BACnet
10
ENUM
Value
Description
Temperature/ Humidity
sensor selection.
Initial delay to start control
after power cycle.
When Smoke Monitor
state is on, the unit
operates as configured
through smoke mode
31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents