Honeywell TC500A Integration Manual page 60

Hide thumbs Also See for TC500A:
Table of Contents

Advertisement

Name
no_ActiveAuxHeatStages
no_HeatCtrlOut
no_ActiveCompHeatStag
es
no_DaHilimit
no_CompDaHilimit
no_IsCoolDisable
no_ActiveCoolStages
no_ReversingVlv
no_CompDaLolimit
no_FanStart
no_FanSpd
no_FanHiSpd
no_FanLoSpd
no_SpaceTemp
no_SpaceHumidity
60
Table 29:
General network outputs
Default
Range
Value
0-2 Stages
0 Stage
0-100%
0%
0-3 Stages
0 Stage
0=Normal
Normal (0)
1=HiLimit
0=Normal
Normal (0)
1=HiLimit
0=Enable
Enable (0)
1=Disable
0-3 Stages
0 Stage
0=Close
Close (0)
1=Open
0=Normal
Normal (0)
1=LoLimit
0=Off
Off (0)
1=On
0-100%
0%
0=Off
Off (0)
1=On
0=Off
Off (0)
1=On
-40~140 Deg
Null
F
0-100 %
Null
(Continued)
BACnet
BACnet
Object
Point Type
Instance
ID
BACnet
8
Numeric
Output
BACnet
9
Numeric
Output
BACnet
10
Numeric
Output
BACnet
13
Boolean
Output
BACnet
14
Boolean
Output
BACnet
15
Boolean
Output
BACnet
11
Numeric
Output
BACnet
16
Boolean
Output
BACnet
17
Boolean
Output
BACnet
19
Boolean
Output
BACnet
12
Numeric
Output
BACnet
20
Boolean
Output
BACnet
21
Boolean
Output
BACnet
18
Numeric
Output
BACnet
19
Numeric
Output
Description
Active auxiliary heat stages
Modulating Heat Output
Active compressor Stages
Discharge Air High Limit
output
Compressor Discharge Air
High Limit output
Cooling enabled/ disabled.
Active cool Stages
Reversing Valve Output
Compressor Discharge Air
Low Limit output
Fan start command
Variable Fan speed output
Fan high speed command
Fan low speed command
Space Temperature
Space Humidity
General network outputs

Hide quick links:

Advertisement

Table of Contents
loading