Name
Cfg_NetWSHPEnStFail
DetDly
Cfg_NetWSHPEnValFai
lDetEn
Cfg_NetWSHPEnValFai
lFalbck
Cfg_NetWSHPEnValFai
lFxdVal
Cfg_NetWSHPEnValFai
lDetDly
Configuration points for Point sharing
Table 25:
Configuration points for Point sharing
Default
Range
0....3600
900 Sec
Seconds
0 = Disable, 1 =
0
Enable
0 = InvalidValue
0
(Null)
1 =
LastKnownGoo
dValue
2 = FixedValue
0~100 %
nan
0....3600
600 Sec
Seconds
BACnet
Point
Value
Type
Bacnet
Numeric
Value
Bacnet
Boolean
Value
Bacnet
Numeric
Value
Bacnet
Numeric
Value
Bacnet
Numeric
Value
(Continued)
BACnet
Object
Description
Instance
ID
285
Network Fail Detection delay
in seconds
171
Network Fail Detection will be
enabled only if network point
is considered for sharing
286
Network Fail Detection Fall
back value
287
Applicable only if Network Fail
Fall back value is configured
to Fixed value (2)
288
Network Fail Detection delay
in seconds