Key
ni_ServiceHeatCtrl
ni_ServiceRevVlvCmd
ni_ServiceSimpleDehCmd
ni_ServiceSimpleHumCmd
ni_ServiceEconomizerCmd
ni_ServiceOccStatusCmd
ni_ServiceOaDmprCtrl
ni_OccManCom
ni_EmergencyHVACOverrid
e
User configurable network inputs
Table 27:
User configurable network inputs
Options
Default
/ Range
Value
0-100%
0%
0=Cmd
Cmd Off
Off
(0)
1=Cmd
On
0=Cmd
Cmd Off
Off
(0)
1=Cmd
On
0=Cmd
Cmd Off
Off
(0)
1=Cmd
On
0=Cmd
Cmd Off
Off
(0)
1=Cmd
On
0=UnOcc
UnOcc
1=Occ
(0)
0-100%
0%
1=Occupi
5=No
ed
sOverrid
2=Unocc
e
upied
3=Bypass
4=Standb
y
5=No
Override
1=Normal
1=Norm
2=Pressur
al
ize
3=Depres
surize
4=Purge
5=Shutdo
wn
(Continued)
BACnet
BACnet
Object
Point
Instance
Type
ID
BACnet
86
Numeric
Value
BACnet
22
Boolean
Value
BACnet
23
Boolean
Value
BACnet
24
Boolean
Value
BACnet
141
Boolean
Value
BACnet
140
Boolean
Value
BACnet
212
Numeric
Value
BACnet
4
ENUM
Value
BACnet
5
ENUM
Value
Description
Modulating Heating control
configuration network input when
service mode is enabled.
Reversing valve configuration
network input when service mode is
enabled.
Dehumudification configuration
network input when service mode is
enabled.
Humidification configuration
network input when service mode is
enabled.
Economizer command when service
mode is enabled
Occupancy Status command when
service mode is enabled
Outside air damper position when
service mode is enabled.
Network Occupancy Manual
Override Command.
Network emergency override to
override the system operation
manually.