Name
no_EffCoolSp
no_EffSp
no_EffTempMode
no_SetpointSts
no_EffAuxHeatSetpoint
no_IsFanOnly
no_DehumActive
no_HumActive
no_IsHeatDisable
no_IsAuxHeatDisable
no_IsCompHeatDisable
no_ActiveHeatStages
General network outputs
Table 29:
General network outputs
Default
Range
Value
40-120 Deg F
Null
40-120 Deg F
Null
1=Cool Mode
5=Off
2=Reheat
Mode
3=Heat Mode
4=Emergency
Heat
5=Off
1=Occupied
1=Occupie
2=Unoccupied
d
3=Temporary
4=Standby
40-120 Deg F
Null
0=Normal
Normal (0)
1=Fan Only
0=Inactive
Inactive (0)
1=Active
0=Inactive
Inactive (0)
1=Active
0=Enable
Enable (0)
1=Disable
0=Enable
Enable (0)
1=Disable
0=Enable
Enable (0)
1=Disable
0-3 Stages
0 Stage
(Continued)
BACnet
BACnet
Object
Point Type
Instance
ID
BACnet
4
Numeric
Output
BACnet
5
Numeric
Output
BACnet
6
ENUM Value
BACnet
7
ENUM Value
BACnet
6
Numeric
Output
BACnet
7
Boolean
Output
BACnet
8
Boolean
Output
BACnet
9
Boolean
Output
BACnet
10
Boolean
Output
BACnet
11
Boolean
Output
BACnet
12
Boolean
Output
BACnet
7
Numeric
Output
Description
Effective Cooling Setpoint
Effective Setpoint
Effective Temperature Mode
When the setpoint is
adjusted by user,
no_setpointsts shifts to
'Temporary'. When the
setpoint is not adjusted it will
represent the current system
state.
Effective auxiliary heat
setpoint.
Fan Only mode enabled/
disabled.
DehumidificationActive/
Inactive
HumidificationActive/
Inactive
Heating enabled/ disabled.
Auxiliary heating enabled/
disabled
Compressor heating
enabled/ disabled
Active heat Stages