Terminal Input Characteristics Configuration - Honeywell TC500A Integration Manual

Hide thumbs Also See for TC500A:
Table of Contents

Advertisement

Terminal input characteristics configuration

Name
Cfg_OccSensChk
0 = Direct
1 = Reverse
Cfg_DirtyFilterChk
0 = Direct
1 = Reverse
Cfg_AirFlwStsChk
0 = Direct
1 = Reverse
Cfg_ShutdownChk
0 = Direct
1 = Reverse
Cfg_MASensChk
0 = NTC 20K
1 = NTC 10K
Cfg_OASensChk
0 = NTC 20K
1 = NTC 10K
Cfg_DASensChk
0 = NTC 20K
1 = NTC 10K
Cfg_FiltPresChk
0 = 0-5 InWC
1 = 0.2.5 InWC
Cfg_CompCurSen
0~9999 Amps
sMaxAmps
Cfg_FanCurSensM
0~9999 Amps
axAmps
Terminal input characteristics configuration
Table 3:
Terminal input characteristics configuration
Range
Default Value
Direct (0)
Direct (0)
Direct (0)
Direct (0)
NTC 20K (0)
NTC 20K (0)
NTC 20K (0)
0-5 InWC (0)
10 Amps
10 Amps
BACnet
BACnet Point
Object
Type
Instance
ID
BACnet
31
Boolean Value
BACnet
32
Boolean Value
BACnet
33
Boolean Value
BACnet
34
Boolean Value
BACnet
137
Boolean Value
BACnet
138
Boolean Value
BACnet
139
Boolean Value
BACnet
155
Boolean Value
BACnet
220
Numeric Value
BACnet
221
Numeric Value
Description
Occupancy sensor input
characteristics selection
Dirty filter input
characteristics selection
Airflow status input
characteristics selection
Shutdown input
characteristics selection
Temperature Sensor
characteristics selection
Temperature Sensor
characteristics selection
Temperature Sensor
characteristics selection
Filter Pressure
Characteristics selection
Comp Current Sensor
Maximum Range
Fan Current Sensor
Maximum Range
15