Space temperature alarm configuration

Key
Cfg_SpcAlarm_TempH
ighLim
Cfg_SpcAlarm_TempL
owLim
Space temperature alarm configuration
Table 24:
Space temperature alarm configuration
Options /
Default
Range
Value
100~150
125 Deg F
Deg F
0~60 Deg F
35 Deg F
BACnet
BACnet
Object
Point
Instance
Type
ID
BACnet
254
Numeric
Value
BACnet
255
Numeric
Value
Description
This is a user configurable point
shown in HMI/Supervisor/ mobile
app which determines the high limit
after which the space temp alarm
will be generated.
This is a user configurable point
shown in HMI/supervisor/ mobile
app which accepts the low limit
after which the space temp alarm
will be generated.