Diagnostic messages

A.1

Diagnostics alarms

Diagnostic messages
For each diagnostic event, a diagnostic message is output and the ER LED flashes on the module.
The diagnostic messages can, for example, be read from the diagnostic buffer of the CPU.
There can be more than one diagnostics alarm at the same time.
Table A-1
Diagnostic messages, their meaning and possible remedies
Diagnostics mes‐
Channel
sage
error
type
(CET)
Configuration error:
0x0602
Station Stop – No
server module
Configuration error:
0x0602
Module parameter
<potential group> er‐
rors or incorrect ter‐
minal block present
in real slot <slot>
Configuration error:
0x0602
Permissible back‐
plane bus size excee‐
ded
Configuration error:
0x0602
Incorrect backplane
bus configuration in
slot <slot>
Configuration error:
0x0602
Impermissible bus
adapter on interface
module
Configuration error:
0x0602
No server module
IM 155-6 PN HA
Equipment Manual, 09/2021, A5E39262148-AE
Exten‐
Assignment Meaning
ded chan‐
nel error
type
(CET)
0x0693
Configura‐
tion
0x0691
Configura‐
tion
0x0698
Configura‐
tion
0x0699
Configura‐
tion
0x069C
Configura‐
tion
0x069E
Configura‐
tion
No server module was
present during power-up of
an ET 200SP HA station.
The installed terminal block
does not match the configu‐
ration.
The total width of the instal‐
led modules exceeds the per‐
missible assembly length of
1300 mm.
The maximum current de‐
mand of all plugged-in mod‐
ules exceeds 2100 mA.
The accompanying <slot> val‐
ue indicates the slot causing
the error.
The installed bus adapter
does not match the configu‐
ration.
The server module is pulled
during operation of an
ET 200SP HA station.
A
Remedy
Verify that the server module is
correctly installed in the rack.
Ensure that a matching termi‐
nal block is installed.
Verify that the backplane bus
configuration does not exceed
the permissible size.
The server module must be the
last module plugged in (high‐
est permissible slot number:
58).
Check the configuration of the
ET 200SP HA.
Verify that a matching bus
adapter is installed.
Ensure that the server module
is correctly installed in the rack.
45