Technical Specifications - Siemens ET 200SP HA Equipment Manual

Table of Contents

Advertisement

Technical specifications

8.1
Technical specifications
Article number
General information
Product type designation
HW functional status
Firmware version
Vendor identification (VendorID)
Device identifier (DeviceID)
Product function
Engineering with
Configuration control
via dataset
Supply voltage
Rated value (DC)
permissible range, lower limit (DC)
permissible range, upper limit (DC)
Reverse polarity protection
Short-circuit protection
Mains buffering
Input current
Current consumption, max.
Inrush current, max.
I²t
Power
Infeed power to the backplane bus
Power loss
Power loss, typ.
Address area
Address space per module
IM 155-6 PN HA
Equipment Manual, 09/2021, A5E39262148-AE
I&M data
STEP 7 TIA Portal configurable/integrated
from version
STEP 7 configurable/integrated from version
PCS 7 configurable/integrated from version
PCS neo can be configured/integrated from
version
Mains/voltage failure stored energy time
6DL1155-6AU00-0PM0
IM 155-6 PN
FS03
V1.1
02AH
030FH
Yes; I&M0 to I&M3
V16
V5.6
V9.0
V3.0
No
24 V
19.2 V
28.8 V
Yes
Yes
10 ms
700 mA; +19.2 V to +28.8 V DC
5 A
0.36 A²·s; Due to increased mains buffering of 10
ms
7.5 W; no doubling in redundant mode as the in‐
feed power is also designed as redundant
2.4 W
8
35

Advertisement

Table of Contents
loading

This manual is also suitable for:

Im 155-6 pn ha

Table of Contents