Description
The following accessories are available:
• BusAdapter
• Carrier modules
– Carrier for one IM 155‑6 PN HA
– Carrier for two IM 155‑6 PN HA for redundant configuration
• Server module
• Power bus cover
• Labeling strips
• Reference identification label
3.3

Fail-safe I/O modules in the I/O device

3.3.1

Response times for the fail-safe modules

Definition
You need to consider the following maximum response time of the interface module for the
calculation of the response times of the fail-safe modules:
Maximum response time = configured update time + 800 μs (but at least 1.8 ms)
IM 155-6 PN HA
Equipment Manual, 09/2021, A5E39262148-AE
Type
Article number
BA 2×RJ45
6DL1193-6AR00-0AA0
BA 2×FC
6DL1193-6AF00-0AA0
BA 2xLC
6DL1193-6AG00-0AA0
BA LC/RJ45
6DL1 193-6AG20-0AA0 Adapter for glass fiber optic cable with IE FC LC Plug and
BA LC/FC
6DL1 193-6AG40-0AA0 Adapter for glass fiber optic cable with IE FC LC Plug and
BA 2xRJ45VD HA
6GK5 991-2VA00-8AA2 Adapter for connection of an IO device to the PROFI‐
3.3 Fail-safe I/O modules in the I/O device
Function
Adapter for Ethernet cable with RJ45 connector
Adapter for direct connection of the Fast Connect bus
cable
Adapter for glass fiber optic cable with IE FC LC Plug
Ethernet cable with RJ45 connector
direct connection of the Fast Connect bus cable
NET IO system using a 2-wire system with copper wires