There is additionally a channel-specific display of the diagnostics through the corresponding
channel fault/channel status LEDs.
The diagnostics messages can, for example, be read out in the diagnostics buffer of the CPU.
Diagnostic messages are assigned either to one input on a channel-specific basis or to all inputs
as a module message. In the event of diagnostics messages that affect the entire module, all
channels are switched off. For diagnostics messages that relate to individual channels, only the
corresponding analog input is affected.
Table A-1

Diagnostic messages, their meaning and possible remedies

Diagnostics mes‐
Error
sage
code
Channel/compo‐
1F
H
nent temporarily
unavailable
Wire break
6
H
High limit violated 7
H
Low limit violated 8
H
Parameter assign‐
10
H
ment error
Supply voltage
11
H
missing
Hardware inter‐
16
H
rupt lost
Module is faulty
100
H
Short-circuit to
106
H
ground
Short-circuit/over‐
10E
H
load at external
encoder supply
64
Assignment
Meaning
Module
Update of the firmware is being performed or
has been canceled. The module does not
perform any measurements during this time.
Analog input
Impedance of encoder circuitry is too
high
Wire break between the module and sen‐
sor
Channel not connected (open)
Analog input
The analog value is above the overrange.
Short-circuit of input to L+
Analog input
The analog value is below the underrange.
Module
Parameter assignment does not match
the terminal block used
Incorrect parameter assignment
Module
Missing or insufficient supply voltage L+
Module
Error is reported because the events occur
faster than they can be processed in the sys‐
tem
Module
Internal module error has occurred
Analog input
Short-circuit of the analog input to transduc‐
er supply or M
Analog input
Short-circuit of the encoder supply to
ground
Encoder supply overload
Remedy
Restart firmware update
Wait for firmware update
Use a different encoder
type or modify the wiring,
for example, using cables
with a larger cross-section
Connect the cable
Disable diagnostics
Connect the encoder con‐
tacts
Correct the module/encoder
tuning
Correct the module/encoder
tuning
Correct the parameter as‐
signment
Check terminal block
Check wiring of the supply
voltage L+ on the terminal
block
Check the terminal block
type
Replace module
Correct the process wiring
Correct the module/encod‐
er tuning
Check the wiring