The diagnostics display of the RN LED is as follows:
RN LED
No supply voltage or insufficient sup‐
ply voltage at the interface module.
Off
Interface module is deactivated.
Flashes
Interface module is not configured.
ET 200SP HA starts up.
ET 200SP HA parameters are assigned
ET 200SP HA is exchanging data with
an IO controller.
On
7.2.2

ER LED

Definition
The ER LED provides diagnostics information.
Description
The ER LED indicates the following errors:
ER LED
Group fault and group fault for chan‐
nels
Flashes
Configured settings do not match the
actual configuration of the ET 200SP
HA.
Impermissible configuration states
Parameter assignment error in the I/O
module
Note
Configuration errors are only checked when the station starts up and not during a CiR or H-CiR
process.
IM 155-6 PN HA
Equipment Manual, 09/2021, A5E39262148-AE
Meaning
Check the supply voltage or switch it on at the interface module.
Check the backplane bus for short-circuit
Activate the interface module with the configuration software or the
user program.
Configure the interface module with the configuration software.
---
---
Meaning
Evaluate the diagnostics and eliminate the error.
Check the configuration of the ET 200SP HA for missing modules, de‐
fective modules or the presence of non-configured modules.
You can find information about the hardware configuration of the
ET 200SP HA in the system manual ET 200SP HA Distributed I/O System;
System Planning, Hardware Configuration.
Evaluate the display of the module information in HW-Konfig and elim‐
inate the error in the corresponding I/O module.
Displays and interrupts
Remedy
Remedy