November 2019
Note
The device description loaded in the host system must be at the same
revision as this device.
Figure 3-3: Commissioning Tag
A. Device revision
Note
The device description loaded in the host system must be at the same
revision as this device. The device description can be downloaded from the
host system website or
Device Drivers under Product Quick Links. You can also visit
select End User Resources.
3.3
Setting security switch
Prerequisites
Set Simulate and Security switch configuration before installation as shown
in
Figure
The simulate switch enables or disables simulated alerts and simulated
AI Block status and values. The default simulate switch position is
enabled.
The Security switch allows (unlocked symbol) or prevents (locked
symbol) any configuration of the transmitter.
Default security is off (unlocked symbol).
The security switch can be enabled or disabled in software.
Use the following procedures to change the switch configuration:
Quick Start Guide
Emerson.com/Rosemount
3-4.
Quick Start Guide
by selecting Download
Fieldbus.org
and
9