November 2019
6. Change damping.
7. Configure LCD display (if installed).
Quick Start Guide
c) Set the OUT_SCALE high value. This may be elevated or
suppressed for level applications.
d) If L_TYPE is "Indirect", the AI Block may be placed in AUTO
mode to return the device to service. Guided Setup does this
automatically.
a) To use guided setup:
Navigate to Configure > Guided Setup, and select Change
Damping.
Note
Guided Setup will automatically go through each step in
the proper order.
Enter the desired damping value in seconds. The
permitted range of values is 0.4 to 60 seconds.
b) To use manual setup:
Navigate to Configure > Manual Setup > Process Variable
and select Change Damping.
Enter the desired damping value in seconds. The
permitted range of values is 0.4 to 60 seconds.
a) To use guided setup:
Navigate to Configure > Guided Setup, and select Local
Display Setup.
Note
Guided setup will automatically go through each step in
the proper order.
Check the box next to each parameter to be displayed to a
maximum of four parameters. The LCD display will
continuously scroll through the selected parameters.
b) To use manual setup:
Navigate to Configure > Manual Setup and select Local
Display Setup.
Check each parameter to be displayed. The LCD display
will continuously scroll through the selected parameters.