The transmitter will only allow three to five percent URL zero error to be
trimmed. For greater zero errors, compensate for the offset by using the
XD_Scaling, Out_Scaling and Indirect L_Type, which are part of the AI Block.
Procedure
1. To use guided setup:
2. To use manual setup:
22
a) Navigate to Configure > Guided Setup and select Zero Trim.
b) The method will execute the zero trim.
a) Navigate to Overview > Calibration > Sensor Trim and select
Zero Trim.
b) The method will execute the zero trim.
November 2019
Rosemount 2051HT