Mitsubishi Electric FR-F 700 EC Instruction Manual page 47

Hide thumbs Also See for FR-F 700 EC:
Table of Contents

Advertisement

Start/stop from the operation panel (PU
operation mode)
9.
Acceleration → constant speed
Perform 20mA input.
The frequency value on the indication increases
according to Pr. 7 Acceleration time until 50.00Hz
is displayed.
10.
Deceleration
Perform 4mA input.
The frequency value on the indication
decreases according to Pr. 8 Deceleration time
until 0.00Hz is displayed and the operation
status indication of FWD or REV flickers.
The motor stops.
11.
Stop
Press
.
FWD or REV of the operation status indication
turns off.
REMARKS
Pr. 184 AU terminal function selection must be set to "4" (AU signal) (initial value). (Refer to
Change the frequency (50Hz) at the maximum value of potentiometer (at 20mA)
Adjust the frequency in Pr. 126 Terminal 4 frequency setting gain frequency. (Refer to page 48.)
Change the frequency (0Hz) at the minimum value of potentiometer (at 4mA)
Adjust the frequency in calibration parameter C5 Terminal 4 frequency setting bias frequency. (Refer to
Instruction Manual (applied).)
40
Operation
Display
Output of the
adjustment meter
(4 to 20mADC)
Output of the
adjustment meter
(4 to 20mADC)
Flickering
Stop
Instruction Manual (applied).)