Mitsubishi Electric FR-F 700 EC Instruction Manual page 136

Hide thumbs Also See for FR-F 700 EC:
Table of Contents

Advertisement

Parameter
Name
C8
Current output bias
(930)
signal
C9
Current output bias
(930)
current
C10
Current output gain
(931)
signal
C11
Current output gain
(931)
current
Parameter copy
989
alarm release
990
PU buzzer control
PU contrast
991
adjustment
Pr.CL
Parameter clear
ALLC
All parameter clear
Er.CL
Alarm history clear
PCPY
Parameter copy
The parameter number in parentheses is the one for use with the parameter unit (FR-PU04).
Incre
Initial
Range
ments
Value
Set the output signal value at the
0.1%
0%
0 to 100%
minimum analog current output.
Set the minimum current value at the
0.1%
0%
0 to 100%
minimum analog current output.
Set the output signal value at the
0.1%
100%
0 to 100%
maximum analog current output.
Set the maximum current value at the
0.1%
100%
0 to 100%
maximum analog current output.
Parameters for alarm release at
parameter copy
10/100
1
10, 100
*17 The setting depends on the inverter
*17
0
Without buzzer
1
1
1
With buzzer
Contrast adjustment of the LCD of the
parameter unit (FR-PU04) can be
1
58
0 to 63
performed.
0 (Light) → 63 (Dark)
Setting "1" returns all parameters except calibration
1
0
0, 1
parameters to the initial values.
1
0
0, 1
Setting "1" returns all parameters to the initial values.
1
0
0, 1
Setting "1" will clear eight past alarms.
0
Cancel
1
Read the source parameters to the operation panel.
1
0
Write the parameters copied to the operation panel to the
2
destination inverter.
3
Verify parameters in the inverter and operation panel.
Extended parameters
Description
capacity (01160 or less/01800 or more)
All
Param
Param
param
eter
eter
eter
copy
clear
clear
: enabled
× : disabled
×
129