Mitsubishi Electric FR-F 700 EC Instruction Manual page 23

Hide thumbs Also See for FR-F 700 EC:
Table of Contents

Advertisement

Wiring
Terminal
Terminal
Symbol
Name
Analog current
CA
output
Analog voltage
AM
output
*1
Low indicates that the open collector output transistor is on (conducts).
High indicates that the transistor is off (does not conduct).
*2
Not output during inverter reset.
(3) Communication
Terminal
Terminal
Symbol
Name
PU
connector
Inverter
TXD+
transmission
TXD-
terminal
Inverter
RXD+
reception
RXD-
terminal
SG
Earth
(4) Control circuit terminal layout
A1
PC
AM
(5) Wiring method
Loosen the terminal screw and insert the cable into the terminal.
Screw Size: M3
Tightening Torque: 0.5N·m to 0.6N·m
2
Cable size: 0.3mm
to 0.75mm
Screwdriver:Small
flat-blade screwdriver (Edge thickness: 0.4mm/
Edge width: 2.5mm)
CAUTION
Undertightening can cause cable disconnection or malfunction.
Overtightening can cause a short circuit or malfunction due to
damage to the screw or unit.
16
Select one e.g. output frequency from
monitor items.
*2
The output signal is proportional to the
magnitude of the corresponding
monitoring item.
With the PU connector, communication can be made through RS-485.
(for connection on a 1:1 basis only)
. Conforming standard : EIA-485(RS-485)
. Transmission format
. Communication speed : 4800 to 38400bps
. Overall length
With the RS-485 terminals, communication can be made through RS-485.
Conforming standard
Transmission format
Communication speed : 300 to 38400bps
Overall length
B1
C1
A2
B2
C2
RL
10E
10
2
5
4
2
Description
Output item:
Output frequency
(initial setting)
Description
: Multidrop
: 500m
: EIA-485(RS-485)
: Multidrop link
: 500m
RM
RH
RT
AU
STOP
1
SE
RUN
SU
IPF
OL
Wire the stripped cable after twisting it to
prevent it from becoming loose. In addition, do
not solder it.
Rated
Specifications
Load impedance
200Ω to 450Ω
Output signal 0 to
20mADC
Output signal 0 to
10VDC
Permissible load
current 1mA
(load impedance
10kΩ or more)
Resolution 8 bit
CA SD PC
RES STF STR PC
FU MRS JOG CS
Cable stripping size
6mm
Refer to
Instruction
Manual
(applied)
Instruction
Manual
(applied).
Refer to
22
22

Advertisement

Table of Contents
loading

Table of Contents