15
|
About the box

15.6 To remove the transportation stay

Installer and user reference guide
54
Accessory pipes (mm)
Liquid pipe
Front connection
ID Øb
ID Øa
Bottom connection
ID Øa
Only for 14~20 HP
NOTICE
If the unit is operated with the transportation stay attached, abnormal vibration or
noise may be generated.
The transportation stay installed over the compressor leg for protecting the unit
during transport must be removed. Proceed as shown in the figure and procedure
below.
1 Slightly loosen the fixing nut (a).
2 Remove the transportation stay (b) as shown in the figure below.
3 Tighten the fixing nut (a) again.
HP
8
10
12
14
16
ID Øb
18
20
3 (12.3 N·m)
3 (12.3 N·m)
1
1
2
2
Øa
9.5
9.5
12.7
12.7
a
b
VRV IV Q+ series heat pump
4P546229-1A – 2020.10
Øb
12.7
15.9
RXYQQ8~20U7Y1B