18.1.7 Multiple outdoor units: Possible layouts

RXYQQ8~20U7Y1B
VRV IV Q+ series heat pump
4P546229-1A – 2020.10
The piping between the outdoor units must be routed level or slightly upward to
avoid the risk of oil retention into the piping.
Pattern 1
a
b
a
b
a
b
a To indoor unit
b Piping between outdoor units
NOT allowed (oil remains in piping)
Allowed
To avoid the risk of oil retention to the outmost outdoor unit, always connect the
stop valve and the piping between outdoor units as shown in the 4 correct
possibilities of the figure below.
a
b
b
a
b
b
a
a
b
a
a
a To indoor unit
b Oil collects to the outmost outdoor unit when the system stops
NOT allowed (oil remains in piping)
Allowed
If the piping length between the outdoor units exceeds 2  m, create a rise of
200 mm or more in the gas line within a length of 2 m from the kit.
b
b
a
b
b
a
18
Piping installation
|
Pattern 2
a
b
a
b
a a
b
Installer and user reference guide