Daikin VRV IV Q+ Series Installer And User Reference Manual page 129

Hide thumbs Also See for VRV IV Q+ Series:
Table of Contents

Advertisement

RXYQQ8~20U7Y1B
VRV IV Q+ series heat pump
4P546229-1A – 2020.10
[2‑26]
Low noise operation start time.
This setting is used in conjunction with setting [2‑22].
[2‑26]
1
2 (default)
3
[2‑27]
Low noise operation stop time.
This setting is used in conjunction with setting [2‑22].
[2‑27]
1
2
3 (default)
[2‑30]
Power consumption limitation level (step  1) via the external control adaptor
(DTA104A61/62).
If the system needs to be running under power consumption limitation conditions
when an external signal is sent to the unit, this setting defines the level power
consumption limitation that will be applied for step 1. The level is according to the
table.
[2‑30]
1
2
3 (default)
4
5
6
7
8
[2‑31]
Power consumption limitation level (step  2) via the external control adaptor
(DTA104A61/62).
If the system needs to be running under power consumption limitation conditions
when an external signal is sent to the unit, this setting defines the level power
consumption limitation that will be applied for step 2. The level is according to the
table.
[2‑31]
1 (default)
Start time automatic low noise operation
(approximately)
20h00
22h00
24h00
Stop time automatic low noise operation
(approximately)
6h00
7h00
8h00
Power consumption limitation (approximately)
60%
65%
70%
75%
80%
85%
90%
95%
Power consumption limitation (approximately)
40%
20
Configuration
|
Installer and user reference guide
129