18
|
Piping installation

18.1.3 To select the piping size

A, B, C: Piping between outdoor unit and (first) refrigerant branch kit
D: Piping between refrigerant branch kits
Installer and user reference guide
72
Determine the proper size using the following tables and reference figure (only for
indication).
a
D
b
c
E
1
2
3
1~4 VRV DX indoor unit
a,b,c Indoor branch kit
x,y Outdoor multi connection kit
Choose from the following table in accordance with the outdoor unit total capacity
type, connected downstream.
Outdoor unit
capacity type
(HP)
Standard
8
19.1
10
22.2
12~16
28.6
18~22
28.6
24
34.9
26~34
34.9
36~42
41.3
Choose from the following table in accordance with the indoor unit total capacity
type, connected downstream. Do not let the connection piping exceed the
refrigerant piping size chosen by the general system model name.
Indoor unit
capacity index
Standard
<150
15.9
150≤x<200
19.1
200≤x<290
22.2
290≤x<420
28.6
420≤x<640
640≤x<920
34.9
≥920
41.3
B
B
A
x
C
y
4
Piping outer diameter size (mm)
Gas pipe
Max.
28.6
34.9
41.3
54.1
Piping outer diameter size (mm)
Gas pipe
Max.
19.1
25.4
28.6
(a)
34.9
54.1
B
Liquid pipe
Standard
Max.
9.5
15.9
9.5
12.7
15.9
19.1
15.9
19.1
22.2
19.1
Liquid pipe
Standard
Max.
9.5
12.7
15.9
12.7
15.9
19.1
19.1
22.2
RXYQQ8~20U7Y1B
VRV IV Q+ series heat pump
4P546229-1A – 2020.10