To Route And Fix The Power Supply; To Connect The Power Supply - Daikin VRV IV Q+ Series Installer And User Reference Manual

Hide thumbs Also See for VRV IV Q+ Series:
Table of Contents

Advertisement

19
|
Electrical installation

19.5 To route and fix the power supply

19.6 To connect the power supply

Installer and user reference guide
116
NOTICE
When routing earth wires, secure clearance of 25  mm or more away from
compressor lead wires. Failure to observe this instruction properly may adversely
affect correct operation of other units connected to the same earth.
The power supply wiring can be routed from the front and left side. Fix it to the
lower mounting hole.
8~12 HP
X1M
c
b
a
a Power supply (possibility 1)
b Power supply (possibility 2)
c Power supply (possibility 3)
d Tie wrap
(a) Knockout hole has to be removed. Close the hole to avoid small animals or dirt from
entering.
NOTICE
Never connect the power supply to transmission wiring terminal block. Otherwise
the entire system may break down.
INFORMATION
Installation and routing in case the cool/heat selector is used: refer to the installation
manual of the cool/heat selector.
14~20 HP
X1M
d
d
A
d
c
A
(a)
(a)
(a)
. Use conduit.
d
A
d
b
a
VRV IV Q+ series heat pump
4P546229-1A – 2020.10
RXYQQ8~20U7Y1B

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents