Daikin VRV IV Q+ Series Installer And User Reference Manual page 152

Hide thumbs Also See for VRV IV Q+ Series:
Table of Contents

Advertisement

24
|
Troubleshooting
Main code
Master
Installer and user reference guide
152
Sub code
Slave 1
Slave 2
Cause
Unusual low pressure on
suction line
Freeze-up prevention indoor
unit
Automatic charging nearly
finished
Automatic charging finished
Solution
Close valve A immediately.
Push BS1 to reset. Check
following items before
retrying autocharge
procedure:
Check if the gas side stop
valve is opened correctly.
Check if the valve of the
refrigerant
cylinder
opened.
Check if the air inlet and
outlet of the indoor unit are
not obstructed.
Close valve A immediately.
Push BS1 to reset. Retry
autocharge procedure.
Prepare for autocharge
stopping.
Finish autocharge mode.