Site Preparation
Table 15: AC power requirements (continued)
Switch Type
Country
BlackDiamond
North America
BlackDiamond
North America
BlackDiamond
International
BlackDiamond
North America
BlackDimamond North America
BlackDiamond
International
BlackDiamond
Australia
• Use appropriate DC power for your switch, as described in Table 16.
Table 16: DC power requirements
Switch Type
Country
Alpine
International
BlackDiamond
International
• Use a vinyl floor covering in your wiring closet. (Concrete floors accumulate dust, and carpets can
cause static electricity.)
• Prevent unauthorized access to wiring closets by providing door locks. Install the equipment in a
secured, enclosed, and restricted-access area, ensuring that only qualified service personnel have
access to the equipment.
• Provide adequate overhead lighting for easy maintenance.
• Ensure that each wiring closet has a suitable ground. All distribution racks and equipment installed
in the closet should be grounded.
• Ensure that all system environmental requirements are met, such as ambient temperature and
humidity.
NOTE
Extreme Networks recommends that you consult an electrical contractor for commercial building and
wiring specifications.
44
Requirements
20 A service receptacle, NEMA L6-20 (locking) for BlackDiamond 110
VAC power supplies.
20 A service receptacle, NEMA L6-20 (locking) for BlackDiamond 220
VAC power supplies.
16 A/20 A service receptacle, IEC 60309 for BlackDiamond 220 VAC
power supplies.
20 A service receptacle, NEMA 5-20 (non-locking) for BlackDiamond 110
VAC power supplies.
20 A service receptacle, NEMA 6-20 (non-locking) for BlackDiamond 220
VAC power supplies.
16 A service receptacle, CEE 7/7 for BlackDiamond 220 VAC power
supplies.
15 A service receptacle, 036 for BlackDiamond 220 VAC power supplies.
Requirements
• Use 30 A at -40 VDC (or equivalent power between -40 and -70 VDC)
for Alpine DC power supplies.
• For Alpine DC power and ground cables, use 8 AWG, high
strand-count copper wire cable (Alpine 3808), 10 AWG, high
strand-count copper wire cable (Alpine 3804), or 14 AWG, high
strand-count copper wire cable (Alpine 3802).
• Use 55 A service for BlackDiamond DC power supplies.
• For BlackDiamond DC power cables, use 4 AWG, high strand-count
copper wire cable.
Extreme Networks Consolidated Hardware Guide