These Advanced Functions, .26 through .50,
are not required for day-to-day use. They
should not be accessed except during set-up
by qualified personnel.
FUNCTION
.26 HEATING OUTPUT LIMIT (OUTPUT 1)
Allows adjustment of maximum output to heater in percent.
Example: if 50% (Option 10) is selected, then the output of the
controller would never be allowed to be greater than 50%. This
might be used with an oversized heater. Autotune can not be used
with SP1 heat limit other than 100% (Option 0). Example: with 10
second cycle time 50% (Option 10) would never allow more than 5
sec on 5 sec off when controller calls for 100% output. Not
applicable if SP1 is ON/OFF.
(Op#).(Fn#)
TABLE 3-6
ADVANCED FUNCTIONS.26 -.50
NOTE
0.26
1.26
2.26
3.26
4.26
5.26
6.26
7.26
8.26
9.26
10.26
11.26
12.26
13.26
14.26
15.26
Parameter/Comment
100% x max output
95%
90%
85%
80%
75%
70%
65%
60%
55%
50%
45%
40%
30%
20%
10%