FUNCTION
.15 RESETTING FUNCTION'S .0 -.24 TO DEFAULT SETTINGS
Allows quick reset of all Functions to Default settings. Only
Function .22 (°C/°F) and Function .9 (Sensor Offset) will not
be reset. NOTE: 'Hidden' Function 15/Option 5 resets all functions,
except Function .22.
(Op#).(Fn#)
0.15
1.15
5.15
.16 INPUT SENSOR SELECT & RANGE TABLE
Selects thermocouple type or RTD. This is the first selection that
must be made for the unit to be used. NOTE: If 3-wire RTD
configuration is ordered, the Pt-100 (Option 9) must be selected.
Option 0 causes the CN9000A to "lock up" (another Option must
be selected to "bring the CN9000A back to life").
Op.Fn Sensor
Type
1.16
J
2.16
K
3.16
N
4.16
R
5 16
S
6.16
T
7.16
E
8.16
J-DIN
9.16
Pt100
10.16
B
(Options cont'd on next page)
Range adjustments (including Default) only limit
setpoint values. Process temperatures will be
displayed over the full linearized range.
TABLE 3-4 (Cont'd)
Parameter/Comment
Normal
Reset (Functions .22 and .9 will not reset)
Resets all functions except Function .22
Default Range
°C
°F
0 to 400
32 to 800
0 to 400
32 to 800
0 to 400
32 to 800
0 to 1600
32 to 1999
0 to 1600
32 to 1999
0 to 250
32 to 500
0 to 500
32 to 1000
0 l0 400
32 to 800
0 to 200
32 to 400
0 to 1600
32 to 1999
NOTE
Linearized Range
°C
0 to 800
32 to 1470
0 to 1200
32 to 1999
0 to 1200
32 to 1999
0 to 1600
32 to 1999
0 to 1600
32 to 1999
-199 to 250
-199 to 480
0 to 600
32 to 1110
0 to 800
32 to 1470
-199 to 400
-199 to 750
0 to 1800
32 to 1999
°F
31