Press and hold in ★ Repeatedly press
4.
(while pressing ★) Repeatedly press
(while pressing ★).
Release ★ (and stop pressing
5.
6.
Press the P button. The temperature is now displayed. The
upper limit of the allowable setpoint has now been changed.
The new allowable setpoint range can be checked by repeating
Steps 1, 2, 3.
Steps 1-6 are repeated in Section 3.5.1.3 for your convenience.
To change the setpoint to the desired value, press ★ and
7.
hold in.
Press
or
8.
Release the ★ button. The temperature is now displayed.
9.
Press the ★ button to check the setpoint value.
10
If an attempt is made to set the setpoint outside of the setpoint
range, the setpoint will be at the end of the range.
SENSOR DEFAULT SETPOINT RANGE TABLE
Fn .16
Option
Type
1
J
2
K
3
N
4
R
5
S
6
T
7
E
8
J DIN
9
Pt100
10
B
Note: If the Default setpoint range maximum is not suitable, it can
be increased or decreased to any desired value within the
linearized band
to change the setpoint to the new value.
NOTE
TABLE 3-3
Iron-Constantan
CHROMEGA
ALOMEGA
®
Nicrosil-Nisil
Pt-13% Rh/Pt
Pt-10% Rh1Pt
Copper-Constantan
CHROMEGA
-Constantan
®
Iron-Constantan
100
Pt RTD(
Pt-30% Rh/Pt-6% Rh
to increase value
to decrease value
or
button).
°C
0-400
0-400
®
0-400
0-1600
0-1600
0-250
0-500
0-400
=0.00385)
0-200
0-1600
Min/Max
°F
32-800
32-800
32-800
32-1999
32-1999
32-500
32-1000
32-800
32-400
32-1999
17