Codes
Coding level 2
(cont.)
Coding in the delivered condition
65:...
Information on the type of diverter
valve (never adjust; specified by
the boiler coding card)
67:40
For solar DHW heating: set DHW
temperature 40 °C. Reheating is
suppressed above the selected set
temperature (boiler only starts as
backup if the rise in the cylinder
temperature is too low).
6C:100
Set speed of internal circulation
pump for DHW heating 100 %
6F:...
Max. heating output for DHW heat-
ing in %; specified by the boiler
coding card
71:0
DHW circulation pump: "ON" ac-
cording to time program
72:0
DHW circulation pump: "ON" ac-
cording to time program
73:0
DHW circulation pump: "ON" ac-
cording to time program

Solar

Coding
Coding in the delivered condition
00:8
Start temperature differential for
solar circuit pump 8 K.
01:4
Stop temperature differential for
solar circuit pump 4 K.
02:0
Solar circuit pump not speed-con-
trolled
03:10
Temperature differential for the
start of the speed control 10 K.
04:4
Controller amplification of speed
control 4 %/K.
05:10
Min. speed of the solar circuit
pump 10 % of max. speed
54
Possible change
67:0
Set DHW temperature adjustable
to
from 0 to 95 °C (limited by boiler-
67:95
specific parameters)
6C:0
Set speed adjustable from 0 to
to
100 %
6C:100
6F:0
Max. heating output for DHW heat-
to
ing adjustable from min. heating out-
6F:100
put to 100 %
71:1
"OFF" during DHW heating to set
value 1
71:2
"ON" during DHW heating to set val-
ue 1
72:1
"OFF" during DHW heating to set
value 2
72:2
"ON" during DHW heating to set val-
ue 2
73:1
"ON" from once per hour for 5 min
to
up to 6 times per hour for 5 min dur-
73:6
ing the time program
73:7
Constantly "ON"
Possible change
00:2
Start temperature differential adjust-
to
able from 2 to 30 K.
00:30
01:1
Stop temperature differential adjust-
to
able from 1 to 29 K.
01:29
02:1
Solar circuit pump is speed-control-
led with wave packet control (do not
adjust)
02:2
Solar circuit pump speed-controlled
with PWM control
03:5
Temperature differential adjustable
to
from 5 to 20 K.
03:20
04:1
Controller amplification adjustable
to
from 1 to 10 %/K.
04:10
05:2
Min. speed of solar circuit pump ad-
to
justable from 2 to 100 %.
05:100